Mfg Part Number: WC375 14 008
Alternate P/N: WC37514008
NSN : 5925-01-122-0698
NIIN : 011220698
CAGE Code : 81348
Manufacturer: Federal Specifications
Item Name : Circuit Breaker Circuit Breaker
FSC : 5925 Circuit Breakers
Our website offers a number of parametric search capabilities, one of which allows you to search specifically for NSN parts. This means you can quickly sort through National Stock Numbers such as 5925011220698 and find parts like part number WC375 14 008 from quality manufacturers like Federal Specifications and many others. To begin the purchasing process immediately, submit an RFQ today. Our team of dedicated account managers is standing by and will respond to all inquiries in 15 minutes or less.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-122-0698 Item Description: CIRCUIT BREAKER | 5925 | 011220698 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
WC375/14-008 | 5 | 2 | 2 |
MRC | Criteria | Characteristic |
---|---|---|
ADAU | BODY HEIGHT | 2.812 INCHES NOMINAL |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
SR-1 | NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | W-C-375/14 |
CPRQ | RESET METHOD | MANUAL |
ADAQ | BODY LENGTH | 3.094 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
SR-1 | SPEC/STD CONTROLLING DATA | |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
AKPX | POLE QUANTITY | 2 |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
ADAT | BODY WIDTH | 2.000 INCHES NOMINAL |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
SR-1 | MANUFACTURERS CODE | 81348 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | TERMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 2 COMPRESSION AND 2 QUICK DISCONNECT, MALE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
AJEC | BOSS HEIGHT | 0.280 INCHES NOMINAL |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/14 GOVERNMENT SPECIFICATION |
AFJN | III FRAGILITY FACTOR | MODERATELY RUGGED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
SR-1 | DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | WC375/14-008 |