Mfg Part Number: THQB2150
NSN : 5925-00-175-4023
NIIN : 001754023
CAGE Code : 60969
Manufacturer: General Electric Inc
Item Name : Circuit Breaker Circuit Breaker
FSC : 5925 Circuit Breakers
Our website offers a number of parametric search capabilities, one of which allows you to search specifically for NSN parts. This means you can quickly sort through National Stock Numbers such as 5925001754023 and find parts like part number THQB2150 from quality manufacturers like General Electric Inc and many others. To begin the purchasing process immediately, submit an RFQ today. Our team of dedicated account managers is standing by and will respond to all inquiries in 15 minutes or less.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-175-4023 Item Description: Circuit Breaker | 5925 | 001754023 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Thqb2150 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.281 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.000 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 2.359 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 18.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 2 CLIP AND 2 COMPRESSION |
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”. |
We Hope that You Will Visit Us Again the Next Time You Need NSN Parts and Make Us Your Strategic Purchasing Partner.
Request for Quote