Mfg Part Number: CD4-Z296-1W
Alternate P/N: CD4Z2961W
NSN : 5925-01-160-2855
NIIN : 011602855
CAGE Code : L3330
Manufacturer: Heinemann Electric Co Inc
Item Name : Circuit Breaker Circuit Breaker
FSC : 5925 Circuit Breakers
Our website offers a number of parametric search capabilities, one of which allows you to search specifically for NSN parts. This means you can quickly sort through National Stock Numbers such as 5925011602855 and find parts like part number CD4-Z296-1W from quality manufacturers like Heinemann Electric Co Inc and many others. To begin the purchasing process immediately, submit an RFQ today. Our team of dedicated account managers is standing by and will respond to all inquiries in 15 minutes or less.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-160-2855 Item Description: Circuit Breaker | 5925 | 011602855 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Cd4-Z296-1w | 5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 5.844 INCHES NOMINAL |
ADAT | BODY WIDTH | 3.096 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.546 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.032 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.031 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.218 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.609 INCHES NOMINAL |
AKPX | POLE QUANTITY | 4 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC FIRST LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FOURTH LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC THIRD LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FIRST LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY FOURTH LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY THIRD LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FIRST LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FOURTH LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT FOURTH LOCATION AND 10.000 MAXIMUM AT 200 PCT FOURTH LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT SECOND LOCATION AND 10.000 MAXIMUM AT 200 PCT SECOND LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT THIRD LOCATION AND 10.000 MAXIMUM AT 200 PCT THIRD LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
FREQ | FREQUENCY IN HERTZ | 400.0 FOURTH LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 SECOND LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 THIRD LOCATION |
FREQ | FREQUENCY IN HERTZ | 440.0 FIRST LOCATION |
TEST | TEST DATA DOCUMENT | 49956-G166010 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAW |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 10 THREADED STUD |
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”. |
We Hope that You Will Visit Us Again the Next Time You Need NSN Parts and Make Us Your Strategic Purchasing Partner.
Request for Quote